PHYM tank pressure foam fire extinguishing device maintenance recommendations

Basic methods and precautions for maintenance
1. Always check whether the flange cover is sealed and whether each valve action is flexible and reliable.
2. When filling the foam extinguishing agent, the tank should be kept clean, and must not be mixed with oil or other foam extinguishing agents. It should not be mixed with the aging foam extinguishing agent.
3, foam fire extinguishing agent can not let direct sunlight, and stored in a small temperature difference, less contact with the air. Where the foam fire extinguishing agent is stored for more than two years, it should be sampled and tested before use. For failure of foam fire extinguishing agents should be updated. Also record the date of replacement of the new foam extinguishing agent.
4. Tanks with capsules should be leak tested once every six months. The test method is to open the drain valve 9. If a foam fire extinguisher leaks, it proves that the capsule is damaged and should be repaired or replaced in time.
5. When changing the firefighting agent, a foam injection simulation test shall be conducted on the fire extinguishing system to check whether the working conditions of the fire pump, the proportioning device and the foam generator are normal and reliable, and if any abnormality should be promptly overhauled.
6. When replacing failed firefighting agents, the device should be thoroughly cleaned. The method of cleaning the capsules is:
(1) First drain off the remaining foam liquid in the capsule, then open the water chamber drain valve 9, then turn on the compressed air (pressure 0.02-0.1 MPa) from the capsule deflation valve 7, open the lower drain valve 6 of the can, and put the foam in the capsule The residual liquid is blown away.
(2) Close the valve 6, open the valve 8, fill the capsule with clean water from the filling port 5 and clean the inner surface of the capsule, then open the valve 6, connect the compressed air from the valve 7 to squeeze out the water, and continue to blow the capsule with compressed air. In ten minutes, thoroughly dry the water in the capsule and re-fill the foam extinguishing agent.

Note: If the screw is rusty, it must be replaced. The rust is so severe that it must be broken with a serrated saw. If it is in the foam tank next to the tank, do not use a chainsaw to prevent accidents!